The device is designed to control motor actuators of mixed valves, in accordance with the water temperature directed to the heating system. It can be used also to keep the temperature in buffers or water tanks heated by a boiler by means of a mixed valve.
Power supply: 230V/50Hz
Temperature sensors: Pt1000 (-50°С ~ +250°С)
Room thermostat input: 0~10V,(4~20mA), contact
Two way actuator output: 220V/50W ; ~24V/2.5W
Proportional actuator output: 24V/2.5W
Circulation pump output switching contact: 220V/3A
Control signal 0~10V/max.20mA
Measurement range: -30°С ~ +130°С
Unit of measurement: 1°С
Humidity: up to 80%
Protection: IP20